Fagor alarm 4010: Overvoltage at the power bus (drive errors 304/306; 4011 = undervoltage, error 307)

CNC 8055 SERCOS drive error (DDS) · Fagor DDS drives

What it means

DC-bus voltage rose above the hardware/software threshold - braking energy cannot be absorbed, or line supply is abnormal.

Likely causes

  • external/internal ballast (braking) resistor open-circuit or burnt
  • power supply module ballast/crowbar circuit failed
  • mains spikes or heavily unbalanced/regenerative line (4011: mains <380 V, loose bus bars, blown PS fuse)

Triage note: Ohm-out the ballast resistor cold - an open ER resistor is the classic cause on vertical axes with fast decel. Undervoltage twin (4011/E307) points instead to line side: torque bus-bar screws and measure under load.

Replacement parts

We supply the following units for this alarm — tested, warranty-backed:

  • ER+TH

    External ballast resistor with thermostat · Primary suspect

    Request a quote →
  • PS-25B4 / XPS-25 (rating-match)

    Power supply module (crowbar/ballast stage) · Common cause

    Request a quote →
  • CM 1.60

    Capacitor module (weakened bus buffering) · Check if others ruled out

    Request a quote →