Fagor alarm 4011: Undervoltage at the power bus (307)
CNC 8055 SERCOS drive error (DDS) · Fagor DDS drives
What it means
Drive standard error E307: the software has measured a DC bus voltage below the permissible minimum. It is a resettable error producing a category 1 controlled stop, with the usual CNC shutdown of enables and program. Check the mains side before blaming the drive.
Likely causes
- Mains voltage below rated value (<380 V AC nominal systems)
- Excessive line impedance under high current peaks
- Loose bus plates, blown PSU fuse or missing line phase
- Regenerative power supply module failing under load