Fagor alarm E304: Power bus voltage too high (with E215 hard-trip and E306 software variants)

DDS drive display code (seven-segment; PS/XPS/RPS power supplies) · Fagor PS/XPS/RPS

What it means

DC bus exceeded limit because regenerated braking energy has nowhere to go - ballast circuit open or undersized. XPS/PS front-panel LED table (red steady) covers the same failures on older units without numeric display.

Likely causes

  • external ballast resistor ER+TH burnt open (thermostat tripped permanently)
  • internal ballast connection bridge missing after module swap
  • crowbar/braking IGBT in PS/XPS failed short-open
  • vertical-axis decel energy exceeding ballast capacity

Triage note: Check thermostat continuity in ER+TH - a tripped stat reads open and mimics a burnt resistor. Verify bus-bar torque while inside; arcing bus joints produce the same trip.