Fagor alarm E316: Compact drive DC bus took too long to charge

DDS drive display code (seven-segment; PS/XPS/RPS power supplies) · Fagor PS/XPS/RPS

What it means

In compact drives (ACD/SCD/CMC), the SoftStart-type charge of the DC bus exceeded the 4-second allowance, so startup was aborted. The manual directs verifying the crowbar (internal or external) connection, the condition of the internal crowbar/SoftStart resistor, and the internal current-limiting fuse in that circuit. This error cannot be disabled.

Likely causes

  • soft-start/crowbar resistor open after years of thermal cycling
  • internal soft-start fuse blown
  • external crowbar wiring loose or wrongly routed
  • excessive capacitive load on the bus (extra CM modules)

Replacement parts

We supply the following units for this alarm — tested, warranty-backed:

  • Soft-start/crowbar resistor (ACD/SCD internal)

    regen-resistor · Common cause

    Request a quote →
  • External ballast/crowbar resistor ER+TH-x/x

    regen-resistor · Check if others ruled out

    Request a quote →