Siemens alarm 300603: Axis %1, drive %2 DC link voltage too high

SINUMERIK 840D/810D powerline drive alarm (SIMODRIVE 611D) · SIMODRIVE 611D/611U

What it means

Reset-class monitor: with dynamic energy management enabled (MD 1165), the measured link voltage (MD 1701) rose above the maximum MD 1163. Unlike the infeed's hard LED-level overvoltage trip, this is the drive-model side of the same physics - braking energy arriving faster than regeneration can export it.

Likely causes

  • regeneration capacity of I/R infeed insufficient for the duty cycle
  • braking resistor/pulsed resistor undersized or failed (UI-type infeeds)
  • MD 1163 threshold set too tight for the application
  • line supply condition limiting regenerative feedback

Triage note: Clears with RESET; if recurrent, log DC link voltage against spindle decel events to prove regen shortfall before replacing hardware.