Siemens alarm 300607: Axis %1 drive %2 current controller at limit

SINUMERIK 840D/810D powerline drive alarm (SIMODRIVE 611D) · SIMODRIVE 611D/611U

What it means

The demanded current setpoint cannot be forced into the motor even with maximum available voltage - per Siemens the classic signature of a phase missing or the motor not connected. Because full voltage with no current response also matches blown bridge hardware, treat it as an electrical-integrity alarm.

Likely causes

  • phase missing: loose/blown motor fuse, open contactor pole, broken motor cable conductor
  • DC link voltage absent (upstream infeed/precharge issue)
  • Uce monitoring tripped inside power section (reset by power cycling)
  • contact between control module and power section interrupted
  • motor winding failure

Triage note: Check motor connection continuity phase-to-phase first; a power-cycle clears Uce latched states before condemning the module.