Siemens alarm 611-IR-LED3-green: Infeed/monitoring module LED 3 (green): device not ready - external enable signal not present (terminals 63/64/48)

SIMODRIVE 611 I/R module LED indication (6SN1145/6SN1146) · SIMODRIVE 611D/611U

What it means

This green indicator is informational, not a fault: the module's self-test passed and low voltages are healthy, but the enable chain from the PLC/NC has not energized terminal 48 (main contactor command), 63 (pulse enable) or 64 (drive enable). The 600 V bus stays off until the enables arrive.

Likely causes

  • normal standby before PLC enables (expected state)
  • PLC user program holding enables off (interlocks, E-stop circuit)
  • open contactor feedback/NS1-NS2 loop or terminal 48 wiring fault
  • broken conductor in the enable wiring harness

Triage note: Trace the enable ladder (terminals 48 -> NS1/NS2 -> 63 -> 64) with the machine's electrical schematic before suspecting the module.