Siemens alarm 611-IR-LEDS-dark: Infeed module shows no LED at all although 3x400 V present (or red LED after X351 restart)

SIMODRIVE 611 I/R module LED indication (6SN1145/6SN1146) · SIMODRIVE 611D/611U

What it means

Either low-voltage converter dead, or the infeed refuses to switch on the 600 V bus because it detects a short circuit on the DC link or on the X351 electronics-power distribution.

Likely causes

  • short circuit on 600 V bus - most frequently a failed spindle power module (6SN1123/6SN1146-based AM)
  • short in low-voltage section via X351 ribbon (one drive's plug-in control board loading the rail)
  • failed low-voltage converter inside infeed itself
  • red LED clearing after unplugging X351 = one drive's regulator plug-in module at fault

Triage note: Isolation procedure: loosen DC-link screws / unplug X351 per module starting from right-hand end until symptom clears - last-disconnected module is the culprit. If unsure whether power module or control board, send pair together for test.