Siemens alarm 611-U-display-A1106: 611U operator display shows steady A1106/B1106 with FAULT LED lit (not flashing)

SIMODRIVE 611 power module front-panel indication · SIMODRIVE 611D/611U

What it means

Steady A1106/B1106 is the normal parameter view of P1106 (power module code) after initialization - it is not itself an alarm; alarms flash. Combined with a constant red FAULT LED it means the drive is stuck not-ready: typically the parameterization was never completed or the FEPROM write (P0652) was missed, sometimes compounded by fault 039 power-section identification mismatch.

Likely causes

  • initialization never finished (P0659=0 state left active, values unsaved)
  • P1106 power module code lost/never stored - FEPROM empty after board swap
  • identification mismatch between board and power module (flashing F039 would confirm)
  • +24 V electronics supply ripple from X351/equipment bus

Triage note: Sequence: exit with P button, POWER-ON reset, verify P1106 against the label/power module list, P0652=1, POWER ON; display should change to ___run.