Siemens alarm 611U-F511: Ground fault detected
SIMODRIVE 611U drive alarm · SIMODRIVE 611D/611U
What it means
The 611U ground-fault test measures whether phase currents exceed response threshold P1167, or whether the shaft moves more than permitted (P1168) during the test - both indicate leakage to earth in the motor circuit. Diagnostics parameter P1169 holds the detailed result.
Likely causes
- insulation fault in motor winding (damp, thermally aged)
- chafed or crushed motor power cable / coolant in connector
- earthed screening braid contacting a phase inside the connector
- measurement asymmetry (false trip) - verify via P1169 and megger test