Siemens alarm 611U-F617: DC link overvoltage
SIMODRIVE 611U drive alarm · SIMODRIVE 611D/611U
What it means
Link voltage exceeded upper limit P1163 (or the dynamic energy management ceiling P1153 from SW 13.1 when P1155 bit 0 is active). Braking energy cannot leave the bus fast enough through regeneration or the braking resistor.
Likely causes
- regenerative feedback unavailable (I/R fault, line condition, terminal 112 setup mode)
- braking resistor absent/open or undersized for the cycle
- load duty with excessive deceleration energy
- thresholds P1163/P1153 set too tight
Replacement parts
We supply the following units for this alarm — tested, warranty-backed:
- Request a quote →
6SN1146-…
regen · Common cause
- Request a quote →
pulsed resistor 6SN1113-…
infeed · Common cause
Need the part urgently?
Send us alarm 611U-F617 with your machine details — typical RFQ turnaround is 24–48h.