Siemens alarm A30502: Power unit: DC link overvoltage

SINAMICS S120 drive warning · SINAMICS S120

What it means

The power unit measured DC-link overvoltage during pulse inhibit, i.e. while the output stage was off yet the bus kept charging - pointing at the supply side rather than regenerating drives. The alarm value carries the bus voltage in 100 mV/bit (compare r0070). Persistent occurrence precedes hard faults and stresses the DC-link capacitors.

Likely causes

  • device supply voltage above the p0210 setting
  • line reactor incorrectly dimensioned (too small)
  • high line voltage transients on an unstable supply
  • misconfigured p0210 relative to actual mains

Triage note: Distinct from fault F30002 (active DC-link overvoltage trip); verify p0210 matches the real line voltage.