Siemens alarm F30002: Power unit: DC link voltage overvoltage
SINAMICS S120 drive fault · SINAMICS S120
What it means
DC link exceeded overvoltage threshold (~800-820 V on a 400 V class system); fault value holds trip voltage in 0.1 V.
Likely causes
- regenerated energy with no/undersized braking resistor or chopper failure
- line supply voltage too high
- line phase interrupted during regeneration
- ramp-down time too short for inertia / Vdc-max controller disabled
- aged/degraded DC-link capacitors raising ripple
Triage note: Correlate trip voltage from r0949 with deceleration events; check p1240/p1121 settings before hardware swaps.