Siemens alarm F30004: Power unit: overtemperature heat sink AC inverter
SINAMICS S120 drive fault · SINAMICS S120
What it means
Heat-sink temperature of the power unit exceeded the permissible limit value (fault value = temperature in 0.01 C).
Likely causes
- fan failure or blocked airflow/filters
- ambient temperature too high
- pulse frequency raised above rated
- sustained overload
- failed heatsink thermistor reporting false high temperature
Triage note: Verify with r0037[0] heatsink temperature at cold start; a hot reading on a cold module points to the sensor, requiring module replacement.