Siemens alarm F30011: Power unit: line phase failure
SINAMICS S120 Line Module fault · SINAMICS S120
What it means
Missing or heavily imbalanced line supply phase at the infeed (ALM/SLM/SML).
Likely causes
- blown input fuse (one phase)
- loose/torched input terminal
- line contactor single-phasing
- grid supply imbalance
Triage note: Check all three phases under load - a marginal connection can measure OK unloaded.