Siemens alarm F30022: Power unit: monitoring U_ce (IGBT collector-emitter voltage)

SINAMICS S120 drive fault · SINAMICS S120

What it means

Saturation voltage of an IGBT outside expected range at operating current - indicates degraded/failing transistor or gate driver.

Likely causes

  • IGBT degradation (thermal cycling ageing)
  • gate-driver failure on power-unit board
  • output short history having stressed the bridge
  • loose power connections generating local heating

Triage note: Practically always ends in replacement of the whole power module; board-level IGBT repair only economical on large chassis units.

Replacement parts

We supply the following units for this alarm — tested, warranty-backed:

  • 6SL3120-… (MM) / 6SL3210-… (PM) / 6SL33xx (chassis power block)

    complete power unit - IGBT bridge not serviced separately · Primary suspect