SINAMICS S120/G150 infeed fault · SINAMICS S120

What it means

DC link could not be pre-charged within the expected time (OFF2, immediate acknowledgement).

Likely causes

  • no/too-low line supply or open line contactor
  • pre-charge resistors blown or overheated (too frequent restarts)
  • short circuit/ground fault on the DC link pulling charge down
  • defective pre-charge circuit (chassis units)
  • ruptured fuse in Motor Module (booksize) preventing bus formation
  • line contactor closed during fast DC-link discharge by braking module

Triage note: Do NOT repeatedly power-cycle: pre-charge resistors overheat and fail, turning a supply issue into major repair. Wait ~8 min between attempts. Field case: blown pre-charge resistors + contactor after rapid restarts, plus 2 of 12 DC-link caps destroyed.