Siemens alarm F30027: Power unit: precharging DC link time monitoring
SINAMICS S120/G150 infeed fault · SINAMICS S120
What it means
DC link could not be pre-charged within the expected time (OFF2, immediate acknowledgement).
Likely causes
- no/too-low line supply or open line contactor
- pre-charge resistors blown or overheated (too frequent restarts)
- short circuit/ground fault on the DC link pulling charge down
- defective pre-charge circuit (chassis units)
- ruptured fuse in Motor Module (booksize) preventing bus formation
- line contactor closed during fast DC-link discharge by braking module
Triage note: Do NOT repeatedly power-cycle: pre-charge resistors overheat and fail, turning a supply issue into major repair. Wait ~8 min between attempts. Field case: blown pre-charge resistors + contactor after rapid restarts, plus 2 of 12 DC-link caps destroyed.