Siemens alarm F30060: Pre-charge contactor state monitoring

SINAMICS S120 drive fault · SINAMICS S120

What it means

Feedback monitoring for the pre-charge contactor (ALM, SLM, BLM diode) or line contactor (BLM thyristor) did not return a correct signal within the monitoring time set in p0255[0]. The binary fault value distinguishes switch-in/out timeout, pre-charge contactor opening during pre-charge/infeed operation, and closing while the drive is OFF. This protects against running the infeed without a proven mains connection path.

Likely causes

  • pre-charge/line contactor worn, welded or not pulling in
  • auxiliary feedback contact or its wiring faulty
  • monitoring time p0255[0] shorter than real contactor response
  • contactor coil control (digital output/relay) failing