Siemens alarm F30061: Bridging contactor monitoring
SINAMICS S120 drive fault · SINAMICS S120
What it means
The bypass (bridging) contactor that shorts out the pre-charge resistor after DC-link charging did not deliver the expected feedback within p0255[1]. Fault-value bits distinguish switching timeout, opening during operation, and closing while OFF/during pre-charge. A bypass that fails to close leaves the pre-charge resistor permanently in circuit, where it overheats; this monitor prevents that condition from going unnoticed.
Likely causes
- bridging/bypass contactor contacts worn or welded
- feedback signal wiring or auxiliary contact faulty
- p0255[1] monitoring time mismatched to contactor response
- contactor coil driver output defective