Siemens alarm F30080: Power unit: Current increasing too quickly

SINAMICS S120 drive fault · SINAMICS S120

What it means

The power unit detected an excessive rate of current rise (di/dt monitor), pointing to a very low-impedance fault path or a control step-response problem. On motors this strongly suggests winding short-circuit or frame fault; on infeeds it appears with heavy charge/discharge currents during line dips or with a missing line reactor. The fault value bit-codes the affected phase U/V/W.

Likely causes

  • motor winding short-circuit or ground fault
  • motor power cables misconnected, shorted or over maximum length
  • missing/incorrectly connected line reactor at the infeed
  • poor line supply quality causing large post-dip charging currents
  • incorrect controller parameterization; defective power unit