Siemens alarm F30650: SI MM: Acceptance test required

SINAMICS S120 drive fault · SINAMICS S120

What it means

Safety Integrated requires an acceptance test before it will release again - the safety system has detected that its checksummed configuration may no longer match the validated state. Causes coded in the fault value include first-time SI commissioning (130), changed boot checksums e.g. after current-controller sampling-time change (1000), wrong reference checksum p9899 (2000), changed safety parameters (2003/2005) and changed hardware-related safety parameters (3003). It produces an acknowledgeable STOP A.

Likely causes

  • safety parameters changed offline or online since last acceptance test
  • SI commissioned for the first time on this module
  • current controller sampling time (p0115[0]) change altered SI clock cycle
  • memory card/Control Unit exchanged with deviating safety data
  • hardware changes affecting the safety configuration

Triage note: Perform the SI acceptance test per 'SINAMICS S120 Function Manual Safety Integrated' and generate the acceptance report.