Siemens alarm F31120: Encoder 1: Power supply voltage fault
SINAMICS S120 encoder fault (Sensor Module / DRIVE-CLiQ encoder) · SINAMICS S120
What it means
A supply problem was detected feeding encoder 1: undervoltage on the sense line, overcurrent on the encoder power or resolver-excitation lines, overloaded 24 V through the Power Module, or overcurrent/overvoltage/hardware fault at the converter's EnDat connection. The manual explicitly warns that interchanging encoder cables 6FX2002-2EQ00-... and 6FX2002-2CH00-... reverses operating-voltage pins and can destroy the encoder.
Likely causes
- wrong or swapped encoder power/signal cable type
- short-circuit or overload in the encoder supply path
- damaged Sense/Sensor Module supply circuitry
- EnDat connection hardware fault in the converter
Triage note: Decode r0949 bit 0-7 to localize; bits 6/7 point to the converter's EnDat driver hardware.